12 17.5 24kV Indoor Vacuum Circuit Breakers, GPVN-E Series
Isimo se-Ambient
Izinga lokushisa le-ambient: -25℃~+45℃, isilinganiso sansuku zonke: ≤35℃
Ukuphakama: 1000m(Okujwayelekile);ingafika ku-4500m ukuze uthole uku-oda okukhethekile;
Umswakamo ohlobene: isilinganiso sansuku zonke ≤95%, isilinganiso sanyanga zonke ≤90%;
Amandla okuzamazama komhlaba ≤8 degree;
Izikhathi ezisebenzayo kufanele zingabi nezinto ezivutha umlilo, iziqhumane, izinto ezonakalisayo kanye nokundindizela okukhulu.
Imodeli
I-GPVN -12Kv/17.5kV Indoor AC High Voltage Vacuum Circuit Breaker
Imininingwane Yezobuchwepheshe
Cha. | Into | Iyunithi | Idatha | ||||||
1 | I-voltage elinganiselwe | kV | 7.2~12(15/17.5) | ||||||
2 | Isilinganiso sokuvama | Hz | 50/60 | ||||||
3 | Ikalwe okwamanje | A | 630,1000,1250 | 1600 | 2000,2500,3150 | 4000 | |||
4 | Ilinganiswe ngokuphuka kwesiyingi esifushane | kA | 20 | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
5 | Ilinganiselwe ukwenza i-short-circuit yamanje | kA | 50 | 63 | 80 | 80 | 100 | 100 | 125 |
6 | Ilinganiselwe isikhathi esifushane ukumelana nokwamanje | kA | 20 | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
7 | Isilinganiso esiphakeme sokumelana namanje | kA | 50 | 63 | 80 | 80 | 100 | 100 | 125 |
8 | Isilinganiso sokunqamuka kokuphuma | kA | 12.6 | 12.6 | 16 | 16 | 20 | ||
9 | Ikalelwe ngaphandle kwesigaba iphutha le- earthing breaking current | kA | 17.4 | 21.7 | 27.4 | 27.4 | 34.7 | 34.7 | 43.5 |
10 | Ilinganiselwe isikhathi sokuphuka kwesiyingi esifushane | Izikhathi | 50 | 30 | 30 | 12 | |||
11 | Ilinganiswe ngokulandelana komsebenzi | O-0.3s-CO-180s-CO | O-180s-CO-180s-CO | ||||||
12 | Isilinganiso sokuphulwa kwebhange le-single capacitor bank | A | 630 | ||||||
13 | Ilinganiswe ngokuphuka kwebhange le-back to back capacitor | A | 400 | ||||||
14 | 1 imiz.Imvamisa yamandla imelana ne-voltage | kV | Isigaba ukuya esigabeni/ emhlabeni: 42, phakathi kokuxhumana okuvulekile:48 | ||||||
15 | Umbani umelane ne-voltage | kV | Isigaba ukuya esigabeni/ emhlabeni: 75, phakathi kokuxhumana okuvulekile:85 | ||||||
16 | Impilo yemishini | Izikhathi | 20000 | ||||||
17 | Isikhathi sokuvala | ms | ≤75 | ||||||
18 | Isikhathi sokuvula | ms | ≤60 | ||||||
19 | Isikhathi sokugcina amandla ngaphansi kwe-voltage elinganiselwe | s | ≤10 |
I-Outline Dimension ye-GPVN-12E
I-GPVN-24 □ I-Indoor AC High Voltage Vacuum Circuit Breaker
Ukucaciswa Kwezobuchwepheshe
Cha. | Into | Iyunithi | Idatha | |||
1 | I-voltage elinganiselwe | kV | 24 | |||
2 | Isilinganiso sokuvama | Hz | 50/60 | |||
3 | Ikalwe okwamanje | A | 630 1250 1600 2000 2500 3150 4000 | |||
4 | Ilinganiswe ngokuphuka kwesiyingi esifushane | kA | 20 | 25 | 31.5 | 31.5 |
5 | Ilinganiselwe ukwenza i-short-circuit yamanje | kA | 50 | 63 | 80 | 80 |
6 | Isilinganiso somjikelezo omfishane ukumelana namanje(4s) | kA | 20 | 25 | 31.5 | 31.5 |
7 | Isilinganiso esiphakeme sokumelana namanje | kA | 50 | 63 | 80 | 80 |
8 | Ilinganiselwe ngokuphuma kwesinyathelo samanje | kA |
|
| 12.6 | 12.6 |
9 | Ikalelwe ukuphuka kwephutha lomhlaba elingaphandle kwesigaba | kA | 17.4 | 21.7 | 27.4 | 27.4 |
10 | Izikhathi zokuphuka ezilinganiselwe ze-short-circuit breaking current | Izikhathi | 50 | |||
11 | Ilinganiswe ngokulandelana kokusebenza |
| O-0.3s-CO-180s-CO | |||
12 | Isilinganiso sokuphulwa kwebhange le-single capacitor bank | A | 630 | |||
13 | Ilinganiswe ngokuphuka kwebhange le-back-to-back capacitor bank | A | 400 | |||
14 | 1 imiz.Imvamisa yamandla imelana ne-voltage | kV | 50 | |||
15 | Umbani umelane ne-voltage | kV | 125 | |||
16 | Impilo yemishini | Izikhathi | 20000 | |||
17 | Isikhathi sokuvala | ms | 75 | |||
18 | Isikhathi sokuvula | ms | 60 | |||
19 | Isikhathi sokugcina ngaphansi kwe-voltage elinganiselwe | s | 10 |